The pressure at port pressure of the monitored medium is – depending on the pressure range – on a flat membrane and operated via a lever system and springs on a cascade switch. It guarantees flutterfree switching. The switches operate independent of the position.

If there is no pressure on the membrane the contact 1-2 is closed. Pump or compressor may start.
If the set upper switching point is reached, contact 1-2 opens and contact 1-4 closes. Pump or compressor will be switched off.

Contact 1-2 will only be restored when the pressure on the membrane has dropped to the set lower switching point. The upper and lower switching point can be adjusted with a screwdriver independently. For each switching point, a scale exists.

Upper switchpoint 0,5 …. 8 bar
Lower switchpoint 0,2 …. 7,5 bar
Smallest difference lower

upper / lower end of range

0,3 / 0,5 bar
Max.operating pressure 30 bar
Max. test pressure 40 bar
Standard setting 2 / 6 bar
Connector G 3/8″ Silumin
weight ca. 0,5 kg
Ambient temperature range -20 …. +70°C
Perm. medium temperature 0 …. +70°C
Protection acc.too DIN 40 050/IEC 529 with rubber grommet IP 54 (Standard)
Protection acc.too DIN 40 050/IEC 529 with cable glands M20 IP 65
Rated operating current at AC1 230V 16A
Rated operating current at AC1 400V 10A
Rated operating current at AC15 230V 6A
Rated operating current at DC13 230V 0,1A
Permissible motor power 1  230V 0,55 kW

 