Technical Specifications
Specification | Details |
Function | 1-channel Repeater Power Supply, HART transparent |
Hazardous Area Connection | Input: 4 … 20 mA (from 2-wire transmitters) Location: Zone 0, 1, 2; Div 1, 2 |
Safe Area Connection | Output: 4 … 20 mA (current source) |
Transmitter Voltage | ≥ 16 V at 20 mA |
Output Load | 0 … 550 Ω |
Galvanic Isolation | Input / Output / Power supply. Test voltage 2.5 kV AC. |
Transfer Accuracy | ≤ 10 µA (relative to 16mA span; including non-linearity and temperature influence) |
Response Time | ≤ 500 ms |
Power Supply | 20 … 35 V DC (via terminals or Power Rail) |
Power Consumption | ≤ 1.4 W at 24V DC |
Safety Certifications | ATEX, IECEx, UL, cUL, and others. |
Functional Safety (SIL) | SIL 2 (SIL 3 in redundant configuration) capable (acc. to IEC 61508) |
Ambient Temperature | -20 … 60 °C (-4 … 140 °F) |
Mounting | 35 mm DIN Rail (acc. to EN 60715) |
Reviews