Technical Specifications

 

Specification Details
Function 1-channel SMART Transmitter Power Supply and Splitter
Hazardous Area Connection Input: 4 … 20 mA (from 2/3-wire transmitters or current sources)
Location: Zone 0, 1, 2; Div 1, 2
Safe Area Connection Output 1: 4 … 20 mA (current sink or source)
Output 2: 4 … 20 mA (current sink or source)
Transmitter Voltage ≥ 16 V at 20 mA
Output Load Max. 750 Ω (current source)
Galvanic Isolation Input / Output 1 / Output 2 / Power Supply. Test voltage 2.5 kV AC.
Transfer Accuracy < 10 µA (including calibration, linearity, and temperature drift)
Response Time < 5 ms
Power Supply 20 … 35 V DC (via terminals or Power Rail)
Power Consumption ≤ 2.2 W
Safety Certifications ATEX, IECEx, UL, cUL, NEPSI, and others.
Functional Safety (SIL) SIL 2 capable (acc. to IEC 61508)
Ambient Temperature -20 … 60 °C (-4 … 140 °F)
Mounting 35 mm DIN Rail (acc. to EN 60715)

PEPPERL+FUCHS VAA-4EA-KF-E2

PEPPERL+FUCHS VAA-4EA-KF-ZE/E2