Technical Specifications
Specification | Details |
Function | 1-channel SMART Transmitter Power Supply and Splitter |
Hazardous Area Connection | Input: 4 … 20 mA (from 2/3-wire transmitters or current sources) Location: Zone 0, 1, 2; Div 1, 2 |
Safe Area Connection | Output 1: 4 … 20 mA (current sink or source) Output 2: 4 … 20 mA (current sink or source) |
Transmitter Voltage | ≥ 16 V at 20 mA |
Output Load | Max. 750 Ω (current source) |
Galvanic Isolation | Input / Output 1 / Output 2 / Power Supply. Test voltage 2.5 kV AC. |
Transfer Accuracy | < 10 µA (including calibration, linearity, and temperature drift) |
Response Time | < 5 ms |
Power Supply | 20 … 35 V DC (via terminals or Power Rail) |
Power Consumption | ≤ 2.2 W |
Safety Certifications | ATEX, IECEx, UL, cUL, NEPSI, and others. |
Functional Safety (SIL) | SIL 2 capable (acc. to IEC 61508) |
Ambient Temperature | -20 … 60 °C (-4 … 140 °F) |
Mounting | 35 mm DIN Rail (acc. to EN 60715) |
Reviews